|
NFPA 96*
(Click Here To
Purchase)
Here at "Fire Suppressant School" TM we teach and follow the
NFPA 96 2004 standards.
* Reprinted with permission from NFPA 96
Standard for Ventilation Control and Fire Protection of Commercial
Cooking Operations ©2004, National Fire Protection Association,
Quincy, MA 02269. The reprinted material is not the complete and
official position of the National Fire Protection Association, on
the referenced subject which is represented only by the standard
in its entirety.
11.2 Inspection of
Fire-Extinguishing Systems
11.2.1 An inspection and servicing of the fire-extinguishing system
and listed exhaust hoods containing a constant or fire actuated water
system shall be made at least every 6 months by properly trained and
qualified persons.
11.2.2 All actuation
components, including remote manual pull stations, mechanical or
electrical devices, detectors, actuators, and fire-actuated
dampers, shall be checked for proper operation during the
inspection in accordance with the manufacturer's listed
procedures.
11.2.4 Fusible
links (including fusible links on fire damper assemblies) and
automatic sprinkler heads shall be replaced at least semi-annually,
or more frequently if necessary where required by the
manufacture.
11.3 Inspection of Exhaust
Systems
The entire exhaust shall be inspected by a properly trained,
qualified, and certified
company or person (s) acceptable to the authority having jurisdiction in
accordance with Table 11.3
11.4.5 Fire-extinguishing
systems shall be permitted to be rendered inoperable during the cleaning
process where serviced by properly trained and qualified persons in
accordance with Section 11.3.
11.4.14 Where required,
certificates of inspection and cleaning shall be submitted to the
authority having jurisdiction.
.________________________________________
1.3.2 The authority having
jurisdiction shall determine compliance with this standard and authorize
equivalent deviations from it in all applications.
3.2.5 Shall. Indicates a
mandatory requirement.
3.3.40 Solid Cooking Fuel.
Any solid, organic, consumable fuel such as briquettes, mesquite,
hardwood, or charcoal.
A.3.2.2 Authority Having
Jurisdiction The phrase is used in NFPA documents in a broad
manner, since jurisdictions and approval agencies vary, as do their
responsibilities. Where public safety is primary, the authority
having jurisdiction may be a federal, state, local, or other regional
department or individual such as a fire chief; fire marshal; chief of a
fire prevention bureau, labor department, or health department; building
official; electrical inspector; or others having statutory authority.
For insurance purposes, an insurance inspection department, rating
bureau, or other insurance company representative may be the authority
having jurisdiction. In many circumstances, the property
owner or his or her designated agent assumes the role of the authority
having jurisdiction; at government installations, the commanding officer
or departmental official may be the authority having jurisdiction.
* Reprinted with permission from NFPA 96
Standard for Ventilation Control and Fire Protection of Commercial
Cooking Operations ©2004, National Fire Protection Association,
Quincy, MA 02269. The reprinted material is not the complete and
official position of the National Fire Protection Association, on
the referenced subject which is represented only by the standard
in its entirety.
|